Five-core power cables with PVC insulation

Five-core power cables with PVC insulation

TU U 31.3-31850229-028:2008
TU U 31.3-31850229-010-2004
IEC 60502-1 (1998-11)

 

Application

VVG, VVGz, VBbSHv, AVVG, AVVGz; AVBbSHv, VVGng, VVGzng, VBbSHvng, AVVGzng, AVBbSHvng
(, , , , , , , , , , )
0.66 kV and 1 kV

Cables are designated for power supply and distribution in fixed installations with rated AC voltage 1 kV and 6 kV at frequency 50 Hz at ambient temperature from -40 C to +50 C and relative humidity up to 98% at temperature up to 35 C.

 

Construction

Conductors
Copper or aluminum round single-wire or multicore conductors (class 1, 2 in accordance with GOST 22483-77).

Insulation and core wrapping
Insulation and core wrapping are made from polyvinylchloride (PVC) compound.

Oversheath
Polyvinylchloride (PVC) compound.
Oversheath is made from low risk-of-fire PVC compound for cables with «ng» designation.
Covering «BbSHv» (for cables with «BbSHv» designation)
Armour is made from 2 galvanized steel tapes and PVC compound oversheath is applied over wrapping.

Technical characteristics

Cable Rated voltage, kV main conductors neutral conductor
Number Nominal conductor cross-section, mm Number Nominal conductor cross-section, mm
VVG, VVGng, VVGz 0.66 4 2.5 – 50 1 1.5 – 2. 5
VVGzng 0.66 5 1.5 – 50 - -
VBbSHv, VBbSHvng 0.66 4 6.0 – 50 1 4.0 – 25
VBbSHv, VBbSHvng 0.66 5 6.0 – 50 - -
VVG, VVGng, VVGz 1 4 35 – 185 1 16 - 120
VVGzng, VBbSHv, VBbSHvng 1 5 35 – 185 - -
AVVG, AVVGng, AVVGz, AVVGzng 0.66 5 2.5 – 50 - -
AVBbSHv, AVBbSHvng 0.66 5 6.0 – 50 - -
AVVG, AVVGng, AVVGz, AVVGzng, AVBbSHv,AVBbSHvng 1 5 35 - 185 - -

Insulation resistance calculated for 1 km at temperature 20 C:
Nominal conductor cross-section, mm Insulation resistance, MOhm, no less
1.5 12
2.5 – 4 10
6 9
10 – 185 7

Insulation resistance calculated for 1 km at 20 C indicated at protractedly permissible temperature for the conductors heating at operational period is at least 0.005 MOhm.

Electric resistance of conductors to DC complies with GOST 22483-77.

Cables endure AC voltage test and 50 Hz frequency during 10 minutes.

Nominal voltage, kV Testing voltage, kV
0.66 3.0
1 3.5

Protractedly permissible temperature for the conductors heating: 70 C.

Cables are flame retardant with a single laying.

Cables with «ng» designation have flame-retarding ability when laid in bundles in accordance with DSTU 4237 – 3 – 22 (category A).

Minimal temperature of cable laying without pre-heating: -15 C.

Minimum permissible bending radius of the cable at installation and routing must equal to min. 7.5 outer diameters of the cable.

Maximum permissible temperature for the conductors heating in short circuit mode: 160 C.

Duration of short circuit mode: max. 4 seconds.

Maximum permissible temperature for the conductors heating in emergency mode: 80 C

Operation time of cables in emergency mode do not should be more than 8 hours in 24 hours, or no more than 1000 hours during all service life.

Guarantee period: 5 years from the commissioning date.

The manufacturer can ensure compliance of cable quality with requirements of current technical specification, provided all terms of transportation, storage, installation and use have been observed.

Service life: 30 years.

All products are certified.


Permissible current loads and permissible short-circuit currents for cables

Nominal conductor cross-section, mm Permissible current loads, A Permissible short-circuit currents, kA
five-core cables with neutral conductor lower cross-section five-core cables
above ground under ground above ground under ground
copper conductors cables
1.5 20 26 17 22 0.17
2.5 26 34 22 29 0.27
4.0 34 45 29 38 0.43
6.0 46 54 39 45 0.65
10 61 72 52 61 1.09
16 81 93 69 79 1.74
25 107 121 91 103 2.78
35 131 147 111 125 3.86
50 165 179 140 152 5.23
70 210 220 179 187 7.54
95 255 260 217 221 10.48
120 299 299 254 254 13.21
150 344 338 292 287 16.30
185 392 378 333 321 20.39
aluminum conductors cables
2.5 20 26 17 22 0.18
4.0 27 34 23 29 0.29
6.0 34 41 29 35 0.42
10 47 55 40 47 0.70
16 62 72 53 61 1.13
25 82 93 70 79 1.81
35 101 113 86 96 2.50
50 127 137 108 117 3.38
70 155 166 132 141 4.95
95 190 197 162 168 6.86
120 220 224 187 190 8.66
150 254 255 216 217 10.64
185 291 286 247 243 13.37
Technical Data (reference values)

VVG, VBbSHv,VVGng ,VBbSHvng at rated voltage 0.66 kV
Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
VVG VBbSHv VVGng VBbSHvng VVG VBbSHv VVGng VBbSHvng
4×2.5+1×1.5 11.0 - 11.0 198 - 201 -
4×4.0+1×2.5 12.9 - 12.9 - 286 - 288 -
4×6.0+1×4.0 14.2 18.4 14.2 18.4 391 671 394 676
4×10+1×6.0 17.4 21.6 17.4 21.6 604 943 608 949
4×16+1×10 21.9 26.1 21.9 26.1 939 1358 945 1366
4×25+1×10 26.9 30.7 26.9 30.7 1408 1885 1416 1895
4×25+1×16 26.9 30.7 26.9 30.7 1469 1946 1447 1956
4×35+1×25 30.0 33.6 30.0 33.8 1894 2121 1902 2435
4×50+1×25 30.0 33.8 35.0 38.8 2589 3206 2600 3220
5×1.5 10.0 - 10.0 - 152 - 154 -
5×2.5 11.0 - 11.0 - 209 - 211 -
5×4.0 12.9 - 12.9 - 303 - 305 -
5×6.0 14.2 18.4 14.2 18.4 412 692 415 697
5×10 17.4 21.6 17.4 21.6 647 986 651 992
5×16 21.9 26.1 21.9 26.1 1015 1434 1021 1442
5×25 26.9 30.7 26.9 30.7 1564 2041 1571 2051
5×35 30.0 33.8 30.0 33.8 2111 2642 2120 2653
5×50 35.0 38.8 35.0 38.8 2850 3467 2861 3481



AVVG, AVBbSHv, AVVGng, AVBbSHvng at rated voltage 0.66 kV
Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
AVVG AVBbSHv AVVGng AVBbSHvng AVVG AVBbSHv AVVGng AVBbSHvng
5×2.5 11.0 - 11.0 - 131 - 133 -
5×4.0 12.9 - 12.9 - 180 - 183 -
5×6.0 14.2 18.4 14.2 18.4 223 503 226 508
5×10 17.4 21.6 17.4 21.6 333 672 337 679
5×16 20.4 24.6 20.4 24.6 472 862 477 870
5×25 26.9 30.7 26.9 30.7 766 1244 774 1253
5×35 30.0 33.8 30.0 33.8 1001 1531 1009 1542
5×50 35.0 38.8 35.0 38.8 1344 1961 1355 1975



VVG, VBbSHv,VVGng ,VBbSHvng at rated voltage 1 kV
Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
VVG VBbSHv VVGng VBbSHvng VVG VBbSHv VVGng VBbSHvng
4×35+1×16 30.5 34.3 30.5 34.3 1945 2485 1954 2496
4×35+1×25 30.5 34.3 30.5 34.3 2043 2583 2052 2594
4×50+1×25 35.6 39.4 35.6 39.4 2654 3281 2666 3295
4×50+1×35 35.6 39.4 35.6 39.4 2751 3378 2762 3392
4×70+1×25 40.3 44.1 40.3 44.1 3520 4230 3534 4246
4×70+1×35 40.3 44.1 40.3 44.1 3617 4326 3630 4342
4×95+1×35 46.4 50.2 46.4 50.2 4788 5602 4805 5622
4×95+1×50 46.4 50.2 46.4 50.2 4921 5735 4937 5754
4×120+1×35 50.4 54.2 50.4 54.2 5751 6634 5769 6656
4×120+1×50 50.4 54.2 50.4 54.2 5883 6767 5901 6788
4×120+1×70 50.4 54.2 50.4 54.2 6084 6968 6102 6989
4×150+1×50 55.8 59.6 55.8 59.6 7191 8170 7213 8196
4×150+1×70 55.8 59.6 55.8 59.6 7392 8371 7414 8397
4×150+1×95 55.8 59.6 55.8 59.6 7656 8635 7678 8661
4×185+1×70 61.3 65.1 61.3 65.1 8903 9977 8927 10005
4×185+1×95 61.3 65.1 61.3 65.1 9167 10242 9191 10270
4×185+1×120 61.3 65.1 61.3 65.1 9389 10464 9413 10492
5×35 30.5 34.3 30.5 34.3 2140 2680 2148 2691
5×50 35.6 39.4 34.6 39.4 2883 3510 2895 3524
5×70 40.3 44.1 40.3 44.1 3950 4660 3963 4675
5×95 46.4 50.2 46.4 50.2 5386 6200 5403 6220
5×120 50.4 54.2 50.4 24.2 6570 7554 6588 7476
5×150 55.8 59.6 55.8 59.6 8175 9154 8197 9180
5×185 61.3 65.1 61.3 65.1 10043 11118 10067 11146



AVVG, AVBbSHv, AVVGng, AVBbSHvng at rated voltage 1 kV
Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
AVVG AVBbSHv AVVGng AVBbSHvng AVVG AVBbSHv AVVGng AVBbSHvng
5×35 30.5 34.3 30.5 34.3 1029.0 1569 1038 1580
5×50 35.6 39.4 35.6 39.4 1377.0 2004 1389 2018
5×70 40.3 44.1 40.3 44.1 1786.0 2495 1799 2511
5×95 46.4 50.2 46.4 50.2 2372.0 3186 2388 3206
5×120 50.4 54.2 50.4 54.2 2821.0 3705 2839 3726
5×150 55.8 59.6 55.8 59.6 3467.0 4446 3489 4472
5×185 61.3 65.1 61.3 65.1 4174.0 5248 4198 5276

©