Armoured copper power cables with PVC insulation 1 kV; 6 kV

Armoured copper power cables with PVC insulation

GOST 16442-80
IEC 60502-1 (1998-11)
IEC 60502-2 (1998-03)

 

Application

VBbSHv () 1 kV; 6 kV

Cables are designated for power supply and distribution in fixed installations with rated AC voltage 1 kV and 6 kV at frequency 50 Hz at ambient temperature from -50 C to +50 C and relative humidity up to 98% at temperature up to 35 C, cables are intended for laying in outdoors including.

 

Construction

Conductors
Copper round single-wire or multicore conductors (class 1, 2 in accordance with GOST 22483-77). Copper multicore sector-shaped conductors.

Insulation and oversheath
Insulation and oversheath are made from polyvinylchloride (PVC) compound.
Core wrapping
Polyvinylchloride (PVC) compound.
Screen for 6 kV cables
Electroconductive screen from electroconducting polyvinylchloride (PVC) compound and screen from 2 copper tapes. These tapes are gapped laid.

Covering «BbSHv» (in accordance with GOST 7006-72)
Armour is made from 2 galvanized steel tapes and PVC compound oversheath is applied over wrapping.

Technical characteristics

Cable Number of conductors Nominal conductor cross-section, mm
VBbSHv 1 kV
VBbSHv 6 kV
2, 3, 4
3
6.0 — 240
35 — 240

Electric resistance of conductors to DC complies with GOST 22483.

Insulation resistance calculated for 1 km at temperature 20 C:

-for cables at rated voltage 1 kV:

Nominal conductor cross-section, mm Insulation resistance, MOhm, no less
1 — 1.5 12
2.5 — 4 10
6 9
10 — 240 7

- for cables at rated voltage 6 kV – 50 MOhm.

Insulation resistance calculated for 1 km at 20 C indicated at protractedly permissible temperature for the conductors heating at operational period is at least:

  • at rated voltage 1 kV - 0.005 MOhm;
  • at rated voltage 6 kV - 0.05 MOhm.

Cables endure AC voltage test and 50 Hz frequency during 10 minutes:

  • 3.5 kV – for cables at rated voltage 1 kV;
  • 15 kV – for cables at rated voltage 6 kV.

Cables are flame retardant with a single laying.

Manufactured cable length for cables at rated voltage of 1 kV :

  • manufactured cable length must be min. 450 m for cables with main conductor cross-section 1.5-16 mm;
  • manufactured cable length must be min. 300 m for cables with main conductor cross-section 25-70 mm;
  • manufactured cable length must be min. 200 m for cables with main conductor cross-section 95-240 mm.

Manufactured cable length for cables at rated voltage of 6 kV :

  • manufactured cable length must be min. 450 m for cables with main conductor cross-section 35-70 mm;
  • manufactured cable length must be min. 400 m for cables with main conductor cross-section 92-120 mm;
  • manufactured cable length must be min. 350 m for cables with main conductor cross-section 150-240 mm.

Minimal temperature of cable laying without pre-heating: - 15 C.

Minimum permissible bending radius of the cable at installation and routing must equal to min. 10 outer diameters of the cable for single-core cable, and min.7.5 outer diameters of the cable – for multicore cables.

Protractedly permissible temperature for the conductors heating: 70 C.

Maximum permissible temperature for the conductors heating in short circuit mode: 160 C.

Duration of short circuit mode: max. 4 seconds.

Maximum permissible temperature for the conductors heating in emergency mode: 80 C

Operation time of cables in emergency mode do not should be more than 8 hours in 24 hours, or no more than 1000 hours during all service life.

Guarantee period: 5 years from the commissioning date.

The manufacturer can ensure compliance of cable quality with requirements of current technical specification, provided all terms of transportation, storage, installation and use have been observed.

Service life: 30 years.

All products are certified.


Permissible current loads at rated voltage of 1 kV

Nominal conductor cross-section, mm Permissible current loads, A Permissible short-circuit currents, kA
Single-core cables Double-core cables Three-core cables *
above ground under ground above ground under ground above ground under ground
1.5 29 32 24 33 21 28 0.17
2.5 40 42 33 44 28 37 0.27
4 53 54 44 56 37 48 0.43
6 67 67 56 71 49 58 0.65
10 91 89 76 94 66 77 1.09
16 121 116 101 123 87 100 1.74
25 160 148 134 157 115 130 2.78
35 197 178 166 190 141 158 3.86
50 247 217 208 230 177 192 5.23
70 318 265 226 237 7.54
95 386 314 274 280 10.48
120 450 358 321 321 13.21
150 521 406 370 363 16.30
185 594 455 421 406 20.39
240 704 525 499 468 26.80

* The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.

Permissible current loads at rated voltage of 6 kV

Nominal conductor cross-section, mm Permissible current loads, A Permissible short-circuit currents, kA
above ground under ground
35 135 147 3.86
50 165 175 5.23
70 210 215 7.54
95 255 260 10.48
120 300 295 13.21
150 335 335 16.30
185 285 380 20.39
240 460 445 26.80
Technical Data (reference values)

Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
Nominal voltage 1 kV with round conductor
2×6.0 16.7 474
2×10 18.3 585
2×16 21.3 791
2×25 24.7 1073
2×35 27.4 1350
2×50 30.9 1706
2×70 34.4 2199
2×95 39.0 2876
2×120 41.9 3400
2×150 46.1 4140
2×185 50.1 4969
2×240 56.6 6371
3×6.0 17.4 563
3×10 19.1 715
3×16 22.4 992
3×25 26.4 1405
3×35 28.9 1758
3×50 32.6 2253
4×6.0 18.7 656
4×10 20.6 861
4×16 24.2 1213
4×25 28.7 1737
4×35 31.4 2195
4×50 36.0 2868
3×10+1×6.0 20.6 822
3×16+1×10 23.5 1130
3×25+1×10 27.1 1532
3×25+1×16 28.7 1636
3×35+1×10 29.7 1888
3×35+1×16 30.4 1974
3×35+1×25 31.4 2098
3×50+1×16 33.5 2452
3×50+1×25 34.4 2574
3×50+1×35 36.0 2736
Nominal voltage 1 kV with sector-shaped conductor
3×70 32.8 2912
3×95 36.9 3784
3×120 40.1 4586
3×150 42.7 5533
3×185 46.8 6703
3×240 52.0 8467
4×70 39.8 3841
4×95 41.6 4877
4×120 45.8 5976
4×150 49.2 7241
4×185 53.2 8720
4×240 59.4 11098
3×70+1×25 37.7 3332
3×70+1×35 37.7 3426
3×70+1×50 38.2 3569
3×95+1×35 41.6 4273
3×95+1×50 41.6 4402
3×120+1×35 43.8 5046
3×120+1×70 45.9 5461
3×150+1×50 47.8 6196
3×150+1×70 47.8 6392
3×185+1×50 52.2 7345
3×185+1×90 52.7 7835
3×240+1×70 58.6 9384
3×240+1×120 58.6 9901
Nominal voltage 6 kV with round conductors
3×35 42.1 3204
3×50 45.0 3786
Nominal voltage 6 kV with sector-shaped conductors
3×70 44.6 4061
3×95 47.8 4952
3×120 51.4 5877
3×150 53.5 6850
3×185 56.7 8016
3×240 61.3 9842

©