Aluminum power cables with PVC insulation 1 kV; 6 kV

Aluminum power cables with PVC insulation

GOST 16442-80
IEC 60502-1 (1998-11)
IEC 60502-2 (1998-03)

 

Application

AVVG, AVVGz (A, A) 1 kV; 6 kV

Cables are designated for power supply and distribution in fixed installations with rated AC voltage 1 kV and 6 kV at frequency 50 Hz at ambient temperature from -50 C to +50 C and relative humidity up to 98% at temperature up to 35 C, cables are intended for laying in outdoors including.

AVVGz cables are designated for fixed connection to electric devices at nominal AC voltage up to 0.66 kV at frequency 50 Hz. Cables are used for connection to devices requiring input sealing.

 

Construction

Conductors
Aluminum round single-wire or multicore conductors (class 1, 2 in accordance with GOST 22483-77).
Aluminum multicore sector-shaped conductors.

Insulation and oversheath
Insulation and oversheath are made from polyvinylchloride (PVC) compound.

Core wrapping
Polyvinylchloride (PVC) compound.

Screen for 6 kV cables
Electroconductive screen from electroconducting polyvinylchloride (PVC) compound and screen from 2 copper tapes. These tapes are gapped laid.

Technical characteristics

Cable Number of conductors Nominal conductor cross-section, mm
AVVG 1 kV
AVVGz 1 kV
AVVG 6 kV
1, 2, 3, 4
2, 3, 4
3
1.5 — 240
1.5 — 50
35 — 240

Electric resistance of conductors to DC complies with GOST 22483.

Insulation resistance calculated for 1 km at temperature 20 C:

-for cables at rated voltage 1 kV:

Nominal conductor cross-section, mm Insulation resistance, MOhm, no less
1 — 1.5 12
2.5 — 4 10
6 9
10 — 240 7

- for cables at rated voltage 6 kV – 50 MOhm.

Insulation resistance calculated for 1 km at 20 C indicated at protractedly permissible temperature for the conductors heating at operational period is at least:

  • at rated voltage 1 kV - 0.005 MOhm;
  • at rated voltage 6 kV - 0.05 MOhm.

Cables endure AC voltage test and 50 Hz frequency during 10 minutes:

  • 3.5 kV – for cables at rated voltage 1 kV;
  • 15 kV – for cables at rated voltage 6 kV.

Cables are flame retardant with a single laying.

Manufactured cable length for cables at rated voltage of 1 kV :

  • manufactured cable length must be min. 450 m for cables with main conductor cross-section 1.5-16 mm;
  • manufactured cable length must be min. 300 m for cables with main conductor cross-section 25-70 mm;
  • manufactured cable length must be min. 200 m for cables with main conductor cross-section 95-240 mm.

Manufactured cable length for cables at rated voltage of 6 kV :

  • manufactured cable length must be min. 450 m for cables with main conductor cross-section 35-70 mm;
  • manufactured cable length must be min. 400 m for cables with main conductor cross-section 92-120 mm;
  • manufactured cable length must be min. 350 m for cables with main conductor cross-section 150-240 mm.

Minimal temperature of cable laying without pre-heating: - 15 C.

Minimum permissible bending radius of the cable at installation and routing must equal to min. 10 outer diameters of the cable for single-core cable, and min.7.5 outer diameters of the cable – for multicore cables.

Protractedly permissible temperature for the conductors heating: 70 C.

Maximum permissible temperature for the conductors heating in short circuit mode: 160 C.

Duration of short circuit mode: max. 4 seconds.

Maximum permissible temperature for the conductors heating in emergency mode: 80 C

Operation time of cables in emergency mode do not should be more than 8 hours in 24 hours, or no more than 1000 hours during all service life.

Guarantee period: 5 years from the commissioning date.

The manufacturer can ensure compliance of cable quality with requirements of current technical specification, provided all terms of transportation, storage, installation and use have been observed.

Service life: 30 years.

All products are certified.


Permissible current loads at rated voltage of 1 kV

Nominal conductor cross-section, mm Permissible current loads, A Permissible short-circuit currents, kA
Single-core cables Double-core cables Three-core cables *
above ground under ground above ground under ground above ground under ground
2.5 30 32 25 33 21 28 0.18
4 40 41 34 43 29 37 0.29
6 51 52 43 54 37 4 0.42
10 69 68 58 72 50 59 0.70
16 93 83 77 94 67 77 1.13
25 122 113 103 120 88 100 1.81
35 151 136 127 145 109 121 2.50
50 189 166 159 176 136 147 3.38
70 233 200 - - 167 178 4.95
95 284 237 - - 204 212 6.86
120 330 269 - - 236 241 9.66
150 380 305 - - 273 274 10.64
185 436 343 - - 313 308 13.37
240 515 396 - - 369 355 17.54

* The same and for four-core cables with neutral conductor lower cross-section. For determining of current loads (four-core cables) which are equal to cross-section of four-wire networks in all loads in normal mode this loads must be multiplied by 0.93 coefficient.

Permissible current loads at rated voltage of 6 kV

Nominal conductor cross-section, mm Permissible current loads, A Permissible short-circuit currents, kA
above ground under ground
35 105 110 2.50
50 125 130 3.38
70 155 160 4.95
95 190 195 6.86
120 220 220 9.66
150 250 250 10.64
185 290 285 13.37
240 345 335 17.54
Technical Data (reference values)

Nominal conductor cross-section, mm Nominal overall diameter, mm Weight of 1 km cable, kg
AVVG AVVGz AVVG AVVGz
Nominal voltage 1 kV with round conductor
1×2.5 5.8 - 40 -
1×4.0 6.7 - 54 -
1×6.0 7.1 - 64 -
1×10 7.9 - 82 -
1×16 9.5 - 123 -
1×25 11.7 - 180 -
1×35 12.9 - 220 -
1×50 14.6 - 284 -
1×70 16.4 - 363 -
1×95 18.9 - 486 -
1×120 20.3 - 570 -
1×150 22.2 - 686 -
1×185 24.6 - 845 -
1×240 27.7 - 1074 -
2×2.5 9.8 9.8 89 115
2×4.0 11.6 11.6 121 162
2×6.0 12.5 12.5 142 193
2×10 14.1 14.1 182 250
2×16 16.0 16.0 242 337
2×25 20.9 20.9 378 549
2×35 23.2 23.2 464 682
2×50 27.1 27.1 623 923
2×70 30.6 - 792 -
2×95 35.2 - 1050 -
2×120 38.1 - 1229 -
2×150 41.9 - 1475 -
2×185 46.3 - 1808 -
2×240 52.4 - 2292 -
3×2.5 10.3 10.3 108 128
3×4.0 12.2 12.2 150 182
3×6.0 13.2 13.2 179 218
3×10 14.9 14.9 234 287
3×16 17.0 17.0 320 392
3×25 22.2 22.2 502 632
3×35 24.1 25.1 646 812
3×50 28.8 28.8 839 1068
4×2.5 11.1 11.1 130 148
4×4.0 13.3 13.3 183 213
4×6.0 14.5 14.5 221 257
4×10 16.4 16.4 291 341
4×16 19.1 19.1 419 488
4×25 24.9 24.9 656 779
4×35 27.6 27.6 816 973
4×50 31.8 31.8 1066 1282
5×2.5 12.1 - 152 -
5×4.0 14.6 - 217 -
5×6.0 15.8 - 263 -
5×10 18.0 - 349 -
5×16 20.9 - 490 -
5×25 27.4 - 792 -
3×4.0+1×2.5 13.3 13.3 174 212
3×6.0+1×4.0 14.5 14.5 213 255
3×10+1×6.0 16.4 16.4 277 336
3×16+1×10 19.1 19.1 396 477
3×25+1×10 22.9 22.9 554 658
3×25+1×16 24.0 24.0 606 728
3×35+1×10 25.9 25.9 700 842
3×35+1×16 25.9 25.9 724 853
3×35+1×25 27.6 27.6 782 964
3×50+1×16 29.7 29.7 918 1114
3×50+1×25 30.6 30.6 969 1181
3×50+1×35 31.6 31.8 1013 1273
Nominal voltage 1 kV with sector-shaped conductor
3×70 29.0 - 2397 -
3×95 32.7 - 3170 -
3×120 36.3 - 3946 -
3×150 38.9 - 4848 -
3×185 42.6 - 5909 -
3×240 48.2 - 7622 -
4×70 36.0 - 3206 -
4×95 37.8 - 4211 -
4×120 41.6 - 5200 -
4×150 45.4 - 6443 -
4×185 49.4 - 7853 -
4×240 55.6 - 10123 -
3×70+1×25 33.5 - 2703 -
3×70+1×35 33.5 - 2797 -
3×70+1×50 34.4 - 2962 -
3×95+1×35 37.8 - 3607 -
3×95+1×50 37.8 - 3736 -
3×120+1×35 40.0 - 4342 -
3×120+1×70 41.7 - 4683 -
3×150+1×50 43.6 - 5383 -
3×150+1×70 43.6 - 5579 -
3×185+1×50 48.4 - 6496 -
3×185+1×90 48.9 - 6976 -
3×240+1×70 54.4 - 8373 -
3×240+1×120 54.4 - 8890 -
Nominal voltage 6 kV with round conductors
3×35 40.7 - 2773 -
3×50 43.6 - 3323 -
Nominal voltage 6 kV with sector-shaped conductors
3×70 43.2 - 3602 -
3×95 46.8 - 4502 -
3×120 50.0 - 5345 -
3×150 52.1 - 6295 -
3×185 55.7 - 7479 -
3×240 59.9 - 9202 -

©